Battery Life, Runtime & Peukert's Law Calculator

Model battery runtime, effective capacity degradation under Peukert's Law, Depth of Discharge (DoD) safety derating, and C-rates across lithium and lead-acid chemistries.

📁 Solar🔒 100% Free & Private⚡ Instant Output
Select cell chemistry to load standard Peukert exponent and DoD.
Manufacturer rated capacity (typically at 20-hr or 5-hr rate).
DC voltage of the battery pack.
Power consumption of the appliance or load.
Ideal battery = 1.00; Lithium = 1.05; Lead-Acid = 1.15–1.30.
%
50% for Lead-Acid; 80–90% for Lithium to maximize cycle life.
Chemical derating caused by colder operating conditions.
%
100% for direct DC loads; 85–92% for AC power inverters.

Battery Capacity & Discharge Duration Summary

Estimated Runtime 6.12 Hours ~6 hours 7 minutes
Usable Energy Capacity 1,020 Wh 1,200 Wh total nominal pack
Continuous Current Draw 13.89 A Factoring 90% inverter efficiency
Discharge C-Rate 0.14 C Gentle discharge rate

Chemistry Performance Comparison at Current 150W Load

Chemistry Peukert (k) Safe DoD Estimated Runtime Delivered Energy
Quick Overview & Direct Answer

Battery Life, Runtime & Peukert's Law Calculator: Calculate battery runtime, effective capacity under Peukert. Fast, free, and secure client-side execution in your browser.

Primary Use Solar panel wattage estimation, battery bank sizing, energy payback time
Input Formats Daily kWh usage, sun hours, panel wattage rating
Output Format System size in kW, recommended battery capacity, annual output
Processing Mode 100% Client-Side Solar Modeling
Access Tier Free, unlimited, no sign-up needed

The Physics of Battery Discharge & Peukert's Law

Calculating battery runtime appears deceptively simple: dividing total Amp-hours by the load current. However, in physical electrochemical cells, a battery's delivered capacity is not a static constant. As the rate of discharge increases, chemical reaction kinetics, internal ohmic resistance ($I^2 R$ heat loss), and localized ion depletion at the electrode boundaries severely reduce the actual electrical charge that can be retrieved before the cutoff voltage is reached.

This non-linear capacity degradation was mathematically formulated by German scientist Wilhelm Peukert in 1897:

$C_p = I^k times t$   or rearranged for runtime:   $t = H times left(frac{C}{I times H}right)^k$

Where:

  • $C$ = Rated battery capacity (in Amp-hours) at discharge rating $H$ (typically 20 hours)
  • $I$ = Continuous discharge current (in Amperes)
  • $k$ = Peukert's exponent (a dimensionless property of the chemistry)
  • $t$ = Actual time to full discharge (in hours)

Peukert's Exponent ($k$) Across Cell Chemistries

In a hypothetical ideal battery with zero internal resistance and instantaneous ion diffusion, Peukert's exponent would equal $1.00$—meaning capacity remains completely identical regardless of whether you discharge it over 100 hours or 5 minutes.

  • Flooded Lead-Acid ($k approx 1.20 - 1.30$): Flooded lead-acid batteries suffer from heavy lead sulfate crystallization and electrolyte stratification. Under high-drain loads (such as electric winches or induction cooktops), usable capacity collapses by over 40%.
  • AGM Lead-Acid ($k approx 1.12 - 1.18$): Absorbed Glass Mat batteries bind electrolyte in fiberglass mats, lowering internal resistance and reducing Peukert loss compared to flooded designs.
  • Lithium Iron Phosphate / LiFePO4 ($k approx 1.02 - 1.05$): Modern LiFePO4 cells feature ultra-low internal impedance and rapid lithium-ion intercalations. Because $k$ is close to 1.00, LiFePO4 delivers virtually full rated capacity across high C-rate draws without severe thermal dissipation.

Step-by-Step Worked Numerical Example

Consider an off-grid camper powering an induction burner from a 12V 100Ah battery system:

  • Appliance Load: 600 Watts AC
  • Inverter Efficiency: 90% ($0.90$)
  • Nominal Voltage: 12.0 Volts DC
  • Battery Pack: 100 Ah rated at 20-hour rate ($H = 20text{ hrs}$)

Step 1: Calculate the DC current drawn from the battery:

$P_{text{DC}} = frac{600text{ W}}{0.90} approx mathbf{666.67text{ Watts}}$

$I = frac{P_{text{DC}}}{V} = frac{666.67text{ W}}{12.0text{ V}} approx mathbf{55.56text{ Amperes}}$

Step 2: Contrast runtime between Lead-Acid ($k = 1.25$) and LiFePO4 ($k = 1.05$):

Flooded Lead-Acid ($k = 1.25$, max 50% DoD):

$t_{text{full}} = 20 times left(frac{100}{55.56 times 20}right)^{1.25} = 20 times (0.090)^{1.25} = 20 times 0.0487 approx mathbf{0.974text{ hours}}$

Applying 50% safe DoD limit: $text{Runtime} = 0.974 times 0.50 approx mathbf{0.487text{ hrs}}; (mathbf{29.2text{ minutes}})$

LiFePO4 Lithium ($k = 1.05$, safe 85% DoD):

$t_{text{full}} = 20 times left(frac{100}{55.56 times 20}right)^{1.05} = 20 times (0.090)^{1.05} = 20 times 0.0797 approx mathbf{1.594text{ hours}}$

Applying 85% safe DoD limit: $text{Runtime} = 1.594 times 0.85 approx mathbf{1.355text{ hrs}}; (mathbf{81.3text{ minutes}})$

Even though both batteries have identical "100 Ah" nameplates, the LiFePO4 battery runs for 81 minutes compared to just 29 minutes for lead-acid—nearly 3x longer under heavy loads!

C-Rate & Depth of Discharge (DoD) Cycling Life

The C-Rate measures the speed of battery charging or discharging normalized to its rated capacity:

$text{C-Rate} = frac{text{Current (Amperes)}}{text{Rated Capacity (Amp-hours)}}$

A 100 Ah battery discharged at 100 Amps is operating at 1C (discharging completely in 1 hour). Discharging at 20 Amps represents 0.2C (5 hours). Operating continuously above 0.5C increases cell operating temperature, accelerating solid-electrolyte interphase (SEI) degradation and shortening overall lifespan.

Frequently Asked Questions

Peukert's Law (formulated by Wilhelm Peukert in 1897) expresses the non-linear relationship between discharge current and available capacity. As discharge current increases, internal electrical resistance and chemical diffusion limitations reduce the total usable capacity extracted from the cell: t = H * (C / (I * H))^k, where k is Peukert's exponent.

Lead-acid batteries suffer from slow ion diffusion and high internal resistance, resulting in Peukert exponents between 1.15 and 1.30. Discharging a lead-acid battery at 1C reduces its delivered capacity by 40% to 50%. Lithium Iron Phosphate (LiFePO4) exhibits exceptionally low internal resistance and rapid lithium-ion mobility, yielding an exponent of k ≈ 1.02 to 1.05. LiFePO4 delivers virtually 100% of its rated capacity even under severe high-current loads.

Depth of Discharge (DoD) is the percentage of total battery capacity that has been discharged relative to overall rated capacity. Lead-acid batteries must rarely exceed 50% DoD to avoid rapid sulfation and premature cycle death (yielding ~500 cycles). In contrast, modern LiFePO4 cells safely discharge up to 80%–90% DoD while delivering 3,000 to 6,000 full recharge cycles.

Chemical reaction kinetics slow dramatically in cold environments. At 0°C (32°F), lithium-ion batteries lose roughly 15% to 20% of their usable capacity, while at -20°C (-4°F), capacity drops by over 40%. Additionally, charging lithium batteries below freezing causes metallic lithium plating on the anode, posing catastrophic short-circuit fire risks.